System power must be turned off before
beginning installation
1
Mount thermostat
Position and mount thermostat on wall following
standard installation procedures. Questions on
installation, see Guidelines for Thermostat/Sensor
Locations and Mounting Thermostat and Sensor on
page 5.
When system power is turned on, if the display is
blank, the thermostat is not receiving 24VAC.
3
Provide battery power to remote sensor
and check sensor transmission
Now, remove Battery Tag from remote sensor to
provide power.
The remote sensor will transmit once every 10
seconds for one hour.
Place the sensor on the thermostat for the best
transmitting-receiving conditions.
2
Connect wires to thermostat
Connect wires following standard wiring procedures.
Questions on wiring, see system diagrams on page 7.
24 VAC Requirement
The thermostat must have 24VAC to operate. If a
common wire is connected to terminal C, the
system is providing 24VAC to the thermostat and
the RC/PS switch (S7) should be in the RC posi-
tion. (See Figure 1 on page 5) Proceed to step 3.
If the thermostat does not have a common wire
connected to terminal C, the RC/PS switch must be
in the PS position to allow Power Stealing.
Antenna Wire – When installing the thermostat,
antenna wire must be installed into the wall for
proper communication between the thermostat
and the remote sensor.
QUICK INSTALLATION GUIDE
WIRELESS REMOTE KIT INSTALLATION
installed through wall
Thermostat Antenna Wire
Power Stealing If the HVAC system does not
provide enough power, we recommend connecting
a 150 Ohm, 10 Watt resistor between terminals W
and C of the furnace or Y and C on the air
conditioner or both to increase the power provided.