Blue Commercial Thermostat with
Automatic Heat/Cool Changeover
Option and Damper Control
Model Programming Choices
1F95-0680
7 Day 5/1/1 Day Non-Programmable
www.white-rodgers.com
PART NO. 37-6819A
0811
Single Stage, Multi-Stage, Heat Pump
Installation and Operating Instructions for Model:
APPLICATIONS
THERMOSTAT APPLICATION GUIDE
1F95-0680 Commercial Thermostat
SPECIFICATIONS
To prevent electrical shock and/or equipment damage,
disconnect electric power to system at main fuse or
circuit breaker box until installation is complete.
CAUTION
!
Save these instructions for future use!
FAILURE TO READ AND FOLLOW ALL INSTRUCTIONS
CAREFULLY BEFORE INSTALLING OR OPERATING THIS
CONTROL COULD CAUSE PERSONAL INJURY AND/OR
PROPERTY DAMAGE.
Description
Heat Pump (No Aux. or Emergency Heat) Yes
Heat Pump (with Aux. or Emergency Heat) Yes
Systems with up to 4 Stages Heat, 2 Stages Cool Yes
Heat Only Systems Yes
Millivolt Heat Only Systems – Floor or Wall Furnaces Yes
Cool Only Systems Yes
Gas or Oil Heat Yes
Electric Furnace Yes
Hydronic (Hot Water) Zone Heat – 2 Wires Yes
Hydronic (Hot Water) Zone Heat – 3 Wires Yes
Wired Remote Temperature Sensor (Indoor or Outdoor) Yes
Dual Fuel Damper Control Feature (Heat Pump Mode
Outdoor Remote Re
q
uired
)
Ye s
ATTENTION: MERCURY NOTICE
This product does not contain mercury. However, this prod-
uct may replace a product that contains mercury.
Mercury and products containing mercury must not be
discarded in household trash. Do not touch any spilled
mercury. Wearing non-absorbent gloves, clean up any
spilled mercury and place in a sealed container. For proper
disposal of a product containing mercury or a sealed
container of spilled mercury, place it in a suitable shipping
container. Refer to www.white-rodgers.com for location to
send product containing mercury.
Index Page
Installation 2
Wiring Connections 2
Wiring Diagrams 3
Thermostat Quick Reference 4
Installer Confi guration Menu 5
Operating Your Thermostat 8
Programming 9
Troubleshooting 13
Electrical Rating:
Battery Power . . . . . . . . . . . . . . . . . . . . . . . . . . mV to 30 VAC, NEC Class II, 50/60 Hz or DC
Input-Hardwire . . . . . . . . . . . . . . . . . . . . . . . . . 20 to 30 VAC
Terminal Load . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1.5A per terminal, 2.5A maximum all terminals combined
Setpoint Range . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45 to 99°F (7 to 32°C)
Differential (Single Stage) . . . . . . . . . . . . . . . . . . . . Heat 0.6°F; Cool 1.2°F
Differential (Multi-Stage) . . . . . . . . . . . . . . . . . . . . . Heat 0.6°F; Cool 1.2°F
Differential (Heat Pump) . . . . . . . . . . . . . . . . . . . . . Heat 1.2°F; Cool 1.5°F
Operating Ambient. . . . . . . . . . . . . . . . . . . . . . . . . . 32°F to +105°F (0 to +41°C)
Operating Humidity . . . . . . . . . . . . . . . . . . . . . . . . . 90% non-condensing max.
Shipping Temperature Range . . . . . . . . . . . . . . . . . -40 to +150°F (-40 to +65°C)
Dimensions Thermostat. . . . . . . . . . . . . . . . . . . . . . 4.2"H x 6.4"W x 1.7"D
Przeglądanie stron 0
1 2 3 4 5 6 ... 15 16

Podsumowanie treści

Strona 1 - SPECIFICATIONS

Blue Commercial Thermostat with Automatic Heat/Cool Changeover Option and Damper ControlModel Programming Choices1F95-06807 Day 5/1/1 Day Non-Programm

Strona 2 - INSTALLATION

10PROGRAMMINGEnergy Saving Factory Pre-ProgramThe 1F95-0680 thermostats are programmed with the energy saving settings shown in the table below for al

Strona 3 - WIRING DIAGRAMS

11Automatic Daylight Saving CalculationThe Real Time Clock will adjust automatically for daylight sav-ings time, in the following manner:Increment one

Strona 4 - THERMOSTAT QUICK REFERENCE

12Wired Remote Temperature SensingOne remote temperature sensor can be installed indoor or outdoor and connected to the thermostat by a maximum cable

Strona 5 - INSTALLER/CONFIGURATION MENU

1313Symptom Possible Cause Corrective ActionNo Heat/No Cool/No Fan(common problems)1. Blown fuse or tripped circuit breaker.2. Furnace power switch to

Strona 6

14NOTES

Strona 7

15NOTES

Strona 8 - OPERATING YOUR THERMOSTAT

www.white-rodgers.comSt. Louis, Missouri Markham, OntarioWhite-Rodgers is a divisionof Emerson Electric Co.The Emerson logo is a trademark and service

Strona 9

2Remove Old ThermostatBefore removing wires from old thermostat, mark wires for terminal identifi cation so the proper connections will be made to the

Strona 10 - PROGRAMMING

3WIRING DIAGRAMSFigure 1 – Heat Pump SystemsFigure 2 – Single Stage or Multi-Stage System (No Heat Pump) with Single TransformerHeat Pump ConnectionsI

Strona 11

4Programming and Confi guration Items 1 "System On" indicates when heating or cooling stage is energized. "System On +2" indicates

Strona 12

5INSTALLER/CONFIGURATION MENUPress and hold the Menu button for at least 5 seconds. The display will show item #1 in the table below. Press Menu to ad

Strona 13 - TROUBLESHOOTING

6INSTALLER/CONFIGURATION MENU21 20 18 MENU dS (On) Off Selects Automatic Daylight Saving Time option22 21 19 MENU (OFF)Keypad LockoutL, P, Limit Selec

Strona 14

7INSTALLER/CONFIGURATION MENUspecify. Heating will start 5 minutes early for every 1° of temperature required to reach setpoint. Example: E On is sel

Strona 15

8INSTALLER/CONFIGURATION MENU Record the number you select for future use. Press MENU or RunSched to exit the menu. The security feature you select

Strona 16 - The Emerson logo is a

9To prevent compressor and/or property damage, if the outdoor temperature is below 50°F, DO NOT operate the cooling system.CAUTION!Cooling System1. P