White Rodgers 1F85-277 Instrukcja Naprawy Strona 123

  • Pobierz
  • Dodaj do moich podręczników
  • Drukuj
Przeglądanie stron 122
CZ-4
OPERATION AND WIRING
PURGE TIME
The CZ-4 has a built-in Purge Time after each call is satisfied and
provides a minimum off time before another call is initiated. The
Purge Time is set at 2.5 minutes after all calls for a particular mode
are satisfied or when the Changeover Timer requires a changeover
due to opposing calls.
After all calls are satisfied or the changeover timer activates, the
Purge Timer begins and the heating or cooling, whichever was on,
is deactivated. Typically the fan may be running during this time and
the damper(s) to the last zone(s) calling will remain open to purge
the conditioned air only into those zones that were calling for the
conditioning.
DIP Switch 5 can be set ON to keep the Fan running during the Purge
mode in order to prevent the fan cycling off and back on between
modes. In the instance where the Fan staying ON may create a draft,
and the frequency of opposite calls is minimal this switch can be kept
to OFF.
The CLR PRGE button on the top left of the panel can be pushed to
override the Purge mode and speed installation and checkout. This
button is only active when the System LED is AMBER.
Leading Air Sensor
www.white-rodgers.com