CMM-3U
CMM-3UK
PURGE TIME
The CMM-3U has a built-in Purge Time after each call is satisfied
and provides a minimum off time before another call is initiated. The
Purge Time is set at 2minutes after all calls for a particular mode are
satisfied or when the Changeover Timer requires a changeover due
to opposing calls.
After all calls are satisfied or the changeover timer activates, the
Purge Timer begins and the heating or cooling, whichever was on,
is deactivated. Typically the fan may be running during this time and
the damper(s) to the last zone(s) calling will remain open to purge the
conditioned air only into those zones that were calling for the condi-
tioning. DIP Switch 4 can be set ON to keep the Fan running during
the Purge mode in order to prevent the fan cycling off and back on
between modes. In the instance where the Fan staying on may cre-
ate a draft, and the frequency of opposite calls is minimal this switch
can be kept to OFF.
Minimum On Timer
The CMM-3U also has a minimum on time whenever the compressor
operates in order to prevent frequent short cycling. Once there is a
call for cooling or the compressor on a heat pump, the CMM-3U will
hold that call for a period of 2 minutes.
CHANGEOVER TIMER
Whenever a call is made for either heating or cooling, the change-
over timer is activated in order to track the amount of time heating
or cooling is on. When an opposite call is made after a first call is
existing the changeover timer calculates the amount of time the unit
has already been supplying the first mode in order to determine how
long it will hold off the opposite call. If an opposite call is made shortly
after the first call, the opposite call may be held off for as much as
20 minutes. If the first call or subsequent calls for the first call mode
has had that mode operating for up to 20 minutes already and an
opposite call comes in after 20 minutes, the changeover timer will im-
mediately recognize the opposite call, shutting off the current mode,
enter the purge mode and automatically switch to the opposite mode.
The longer a call has been running up to 20 minutes, the shorter the
wait time will be for an opposite call. If a call is over 20 minutes and
an opposite call is made the changeover will be immediate following
the purge time. This intelligent changeover timing makes the CMM-
3U unique to any other zoning system.
CHECKOUT
The CMM-3U has unique features that simplify the checkout of the
system and has LED readouts that constantly indicate the system op-
eration. Once 24 Volt Power is applied to the panel the Green Power
LED will illuminate.
This will stay illuminated constantly when power is applied. The Sys-
tem LED will provide several different indications based upon color
and if it is flashing.
Heat ON – RED
Heat Limit – RED
Flashing Cool ON - GREEN
Cool Limit - GREEN Flashing
FAN ON - AMBER
PURGE - AMBER Flashing
Each zone has its own small Green indicator LED next to each zone
relay. This light is lit when the specific zoning is calling for the mode
shown on the System LED.
WIRING
The CMM-3U is very simple to wire and requires only a minimum
number of connections. The CMM-3U terminal blocks are color coded
and screw-less for all wires to be easily pushed into their respective
terminal by de-pressing the button for each point and releasing once
the wire is seated. (Solid wire can often just be pushed into the termi-
nal without de-pressing the button.) To remove the wire, just press its
button again and remove the wire.
Zone Dampers – The CMM-3U can power any 24VAC damper, ei-
ther 2 wire or 3 wire. See specific wiring instructions with the damper
or inside panel cover. The three damper motor contacts are for
24VAC power are COM (Common), OPN (Open) and CLS (Closed).
Two wire, spring return, normally open dampers use only COM and
CLS terminals.
COM
OPN
CLS
M1
M4
M6
Zone Thermostats – The thermostats wiring will be for Conventional
single stage (Y-G-R-W-C) or Heat Pump (Y-G-R-E-C and O or B).
See Wiring Diagram 1and 2 each type of thermostat.
WIRING DIAGRAM 1 – Conventional Thermostats
C W R Y G
W2/E
G
Y
R
W/OB
C
CONVENTIONAL THERMOSTAT
WIRING DIAGRAM 2 –
Heat Pump Thermostat
C O/B R Y G W2/E
W2/E
G
Y
R
W/OB
C
HEAT PUMP THERMOSTAT
WIRING DIAGRAM 3 - HVAC Equipment – Single
Stage Heating Cooling with Gas/Electric Heating.
Y1 FIRST STAGE COOL
G FAN RELAY
R 24VAC TRANSFORMER C
W1 FIRST STAGE HEAT RELAY
W2 SECOND STAGE HEATING RELAY
Y1
G
O
W1/B
R
W2
W3/E
ZONE PANEL
TECHNICAL HELP
www.white-rodgers.com