
continue to run in order to adequately provide conditioning for each
mode. If a particular mode has already been calling for 20 minutes or
longer and an opposite call comes in the CMM-3U will immediately
drop the mode, enter the purge mode in order to dissipate the condi-
tioned air into the zones calling before switching over to provide the
new conditioning call to its zones.
When using the CMM-3U to control two stage heating, the second
stage is controlled based upon time after the first stage call from the
thermostat. When any zone calls the panel’s built-in timer begins and
after the set period of time elapses the CMM-3U will also activate the
W for second stage heating. The Second Stage Timer is adjustable
between 2, 4, 8 or 16 minutes after the first stage calls. Once the
second stage is on, it will continue to run until the first stage is satis-
fied.
Once all zone thermostats are satisfied for heating and cooling, the
CMM-3U can now accept Fan calls allowing Continuous Air Circula-
tion (CAC) in those zones where the thermostat’s Fan Switch is set
to ON. These zone dampers will be Open while the dampers to the
zones where the Fan Switch is set to AUTO will be CLOSED.
When all zone thermostats are satisfied for both Heating and Cool-
ing, and all Fan switches are set to AUTO position, the HVAC unit will
be off and all zone dampers will return to a normally open position.
Once a zone calls for heating, cooling or fan, the dampers to the
calling zones remain open and the dampers to the zones not calling
will close.
SET-UP FOR VARIOUS HVAC EQUIPMENT
The CMM-3U is factory set for conventional heating and cooling
operation. The panel only needs to be configured when using with an
electric furnace or heat pumps.
Most all of the panel configuration is done by setting the DIP switches
in the top right of the panel. Other functions come by wiring for spe-
cific applications. Below is shown the most typical settings. Review
each function for you application.
1. SYSTEM – G/E OR HP This switch sets the HVAC Output
operation. In G/E the Y1 operates as first stage cooling only.
In HP position Y1 makes as the compressor call for both
heating and cooling.
2. HP Type – CONV or FF – This switch is used to determine
the equipment output when the System switch is set to HP,
this switch determines if the output will be for a conventional
heat pump with electric back-up heat or fossil (dual) fuel
mode.
3. FAN IN HEAT – YES or NO – This switch will activates the
Fan on a call for Heat in the Yes position. In Off, the heating
unit must activates the fan when the heat is called.
4. FAN PURGE – YES or NO – This switch determine if the Fan
is kept on during the Purge Mode, after the end of each heat
or cool call.
5. STAT RV – O or B – When using HP type thermostats this
determines if the O or B terminal is wired to the W/OB termi-
nal on each thermostat to determine if the call if for Heat (B)
or Cool (O).
6. TSTAT – HC-HP Switch determines if conventional Heat/Cool
thermostats or Heat Pump thermostats are being used for
ALL zones. A conventional HC stat would have separate W
and Y output for heating and cooling calls. A HP thermostat
uses Y for both a heat and cool call and the O or B is used to
determine whether the call is for Cooling (O) or Heating (B).
7. EM HEAT – This switch sets any heat call to call for the Emer-
gency Heat. The Red EM HEAT LED on the panel will light
only when this switch is ON. This is used when there is no
EH switch on the thermostats.
8. TEST – This switch accelerates the panel timings in order to
provide a quick checkout of all of the functions without hav-
ing to wait the full time for each sequence.
One of the many features of the DIP switches is if at anytime the
equipment is changed from single stage to heat pump or vice versa
the thermostats do not need to be changed with the equipment
change. Changing the DIP switch settings is all that is needed.
LEAVING AIR SENSOR (CLAS)
The Leaving Air Sensor, Model CLAS, is a remote sensor that is
located in the supply air duct to sense the Leaving Air temperature
of the HVAC Unit. The LAS is a high limit protection for the heating
and a low limit protection for the cooling. When zoning, the airflow
through the HVAC Unit is critical. The CLAS protects the equipment
in low air flow situations as well as when by-pass air is being directed
back into the return air duct.
The heating limit is adjustable from 110°F to 170°F. The cooling limit
is fixed at 45°F. When the CLAS senses heating above its set point,
or cooling below its set point, the CMM-3U will drop both all stages
of heating or cooling. The CLAS must sense a 10°F fall for heating or
rise for cooling before re-activating the first stages of heating or cool-
ing. If two stage heating or cooling is being used the second stage
timer will start again once the first stage is re-activated.
110
120
130
140
150
160
170
HIGH LIMIT
The CLAS requires 2 wires from the sensor to the LAS terminals on
the CMM-3U panel.
LAS
LAS
OAS
OAS
Leaving Air Sensor
In Supply Air Duct
Outdoor Air Sensor only used with
Fossil/Dual Fuel Applications
OUTDOOR AIR SENSOR (COAS)
The Outdoor Air Sensor is used only when using a Heat Pump with
Dual/Fossil Fuel back-up furnaces. The COAS senses the outdoor
air temperature and switches the heating control between the heat
pump and the fossil fuel furnace. The temperature set point for this
is adjustable on the Outdoor Balance Point (OBP) dial on the control
panel. It is adjustable from 5°F to 53°F. It is suggested that this be set
just above freezing to avoid the heat pump from potentially going into
Defrost mode.
5
13
21
29
37
45
53
OBP
Stage Timer
The CMM-3U has a built-in stage timer that eliminates the need
and added cost of using two stage thermostats. On a call for either
heating the timer begins. Setting the Stage Timer dial provides a
adjustable time delay of 5 to 21 minutes between the first and second
stage calls and the same between a second stage and third stage
call of heating, if used.
5
8
9
12
15
18
21
STAGE TIMER
CMM-3U
CMM-3UKZONE PANEL
www.white-rodgers.com
252
TECHNICAL HELP
Komentarze do niniejszej Instrukcji